Pakiet chłodzenia cieczą LCP Rack CW - Pakiety chłodzenia cieczą
Cooling via high-performance compact impellers. The LCP draws in the air at the sides at the rear of the server enclosures and blows the cooled air back into the front part of the server enclosure at the sides.
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Control of the server inlet temperature
With redundant temperature sensor integrated at the air end as standard
Optimum adaptability due to dynamic, continuous control of the cold water volume flow
By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
Targeted cooling output due to modular fan units
Fan modules configurable as n+1 redundancy
Standard 3-phase connection for electrical redundancy
The separation of cooling and enclosure prevents the ingress of water into the server enclosure
Material:Sheet steel, spray-finished
Colour:RAL 7035
Protection category IP to IEC 60 529:IP 20
Variant:Rack cooling
Total cooling output/Number of fan modules:10 kW / 1 20 kW / 2 30 kW / 3
Number of fan modules in supplied state:1
Total cooling output:30 kW
Air throughput (unimpeded air flow):At 50 Hz: 4,800 m³/h At 60 Hz: 4,800 m³/h
Rated operating voltage:230 V, 1~, 50 Hz/60 Hz 400 V, 3~, 50 Hz/60 Hz
Dimensions:Width: 300 mm Height: 2,000 mm Depth: 1,000 mm
Temperature control:Linear fan control Two-way control valve
To fit:TS IT
Installation in bayed enclosure suite:Flush
Temperature Range:Water inlet: +15 °C
Type of electrical connection:Connector
Duty cycle:1
Permissible operating pressure (p. max.):6
EC fan:yes
Fans may be exchanged with the system operational:yes
Water connections:DN 40 (G 1½" external thread)
eCl@ss 8.0/8.1:27180712
Packs of:1 pc(s)
Weight/pack:194 kg
EAN:4028177661813
Customs tariff number:84158200
ETIM 7.0:EC002515
ETIM 6.0:EC002515
eCl@ss 8.0/8.1:27180712
eCl@ss 6.0/6.1:27180712